How to select a transformer sizing or rating for commercial and industrial ?

Transformer Sizing calculation

Calculate Transformer sizing and Voltage drop  with regulation at starting of large size motor Procedure:- The transformer sizing is done base on the following condition. a) peak load calculated from continuous ,intermittent & standby. b) 10% spare capacity for future loads. c) Load requirement with highest rated Motor started on DOL. 1:-Calculation of total peak load Total connected load as per transformer-sizing-load-summary given below Continuous load (E) Intermittent load (F) Stand by load (G) Total KW 222.74 Total kVR 138.04 Total KVA 262.05 Total KW 1871.61 Total KVAR 1159.92 Total…

Read More